Procedural Considerations
Page 46 34-ST-25-20 MC Toolkit User Manual Release 0
7/03
Honeywell HART Main Menu Procedures
Basic
Setup
Honeywell ST 3000
Transfer Function - Linear or Square Root
(select)
SV Units - Engineering Units for
Secondary Variable (select)
Sensor Type- DP, GP, AP (read):
Honeywell STT 3000
CJT Units - Engineering Units for Cold
Junction Temperature (select)
LRL - Lower Range Limit; URL - Upper Range Limit (read)
LRV - Lower Range Value ; URV - Upper Range Value (enter or read)
PV Sensor Units (r/w) - Engineering Units (select)
Damping - Filtering factor for process "noise" (in seconds - select)
Output
Condition
HART Output
Poll Address
To change the Poll Address
(0-15) of the connected
device:
· Select the desired address
from the pull-down list
· Select the Send button.
Scaled D/A Trim - (Refer to
Table 23 for more
information.)
Alarm Direction - Failsafe
(
Upscale | Downscale)
jumpered or switched in
field device)
NAMUR - Select output
levels:
Standard or NAMUR
Req. Preambles - Number
of preambles required
Alarm
Break Detect - select
Disabled or Enabled
When Enabled, the
transmitter checks for open
Thermocouple.
Latching Alarm - select
Disabled or Enabled
When Enabled, the output
remains in Failsafe until the
critical status condition is
cleared, and the transmitter
is reset.
When Disabled, if the
transmitter goes to Failsafe,
the transmitter will clear
Failsafe as soon as the
critical status condition is
cleared.
Click on the
Clear Latching button to
clear the Failsafe condition
if the Latching Alarm is
Enabled.